ABB
1SDA074649R1XT1N 125 TMF 15-500 4p F F UL/CSA (XT1NU4015AAA000XXX)
XT1N 125 TMF 15-500 4p F F UL/CSA (XT1NU4015AAA000XXX)
Moulded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax XT (UL/CSA) series) - XT1N 125 TMF 15-500 4p F F UL/CSA (XT1NU4015AAA000XXX) - 4-poles (4P4d) - Rated current 15A - Short circuit rating 18kA (600Y/347Vac; UL489) - Thermal-Magnetic (fixed) (TMF) trip unit - Rated voltage 600Y/347Vac - equivalent to XT1N125TMF155004pFFULCSA
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
Brand
SKU
1SDA074649R1
Online Price
$1,331.90
This product is currently in stock. As availability may change very fast due to demand, please order this product as soon as possible to secure your order availability.
1SDA074649R1ABB - Tmax XT UL/CSA
Description
Moulded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax XT (UL/CSA) series) - XT1N 125 TMF 15-500 4p F F UL/CSA (XT1NU4015AAA000XXX) - 4-poles (4P4d) - Rated current 15A - Short circuit rating 18kA (600Y/347Vac; UL489) - Thermal-Magnetic (fixed) (TMF) trip unit - Rated voltage 600Y/347Vac - equivalent to XT1N125TMF155004pFFULCSA
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax XT (UL/CSA)
Sub-range name
XT1N
Functions
Moulded Case Circuit Breaker (MCCB)
Poles
4-poles (4P4d)
Rated current
15A
Trip current rating
15 AT
Frame current rating
125 AF
Rated Voltage (DC)
500Vdc
Rated voltage (AC)
600Y/347Vac
Rated impulse voltage (Uimp)
8 kV
Connection type
Ring-lug or bar connections
Short circuit breaking rating
50kA (240Vac; UL489)
25kA (480Vac; UL489)
18kA (600Y/347Vac; UL489)
25kA (480Vac; UL489)
18kA (600Y/347Vac; UL489)
Trip unit type
Thermal-Magnetic (fixed)
TMF
TMF
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- fixed at 15A
Short-circuit pickup current -- fixed at 500A
Short-circuit pickup current -- fixed at 500A
Operating mode
Toggle
Electrical durability (with load)
8000 operations
Mechanical durability (at no load)
25 000 operations
Order code / Manufacturer SKU
XT1N 125 TMF 15-500 4p F F UL/CSA
XT1NU4015AAA000XXX
XT1NU4015AAA000XXX
Manufacturer product status
Commercialized
Equivalent to
XT1N125TMF155004pFFULCSA
EAN code
8015644786267
UPC code
888614508408
UNSPSC code
39121616
Compliant with standard(s)
UL 489
CSA C22.2
CSA C22.2
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - SACE Tmax XT UL-CSA - Catalogue.pdf | 18 May 2021 | English (US) |
ABB - SACE Tmax XT UL-CSA - Technical characteristics.pdf | 18 May 2021 | English (US) |