ABB
1SDA074746R1XT2N 125 TMA 125-625..1250 3p FF UL/CSA (XT2NU3125BBB000XXX)
XT2N 125 TMA 125-625..1250 3p FF UL/CSA (XT2NU3125BBB000XXX)
Moulded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax XT (UL/CSA) series) - XT2N 125 TMA 125-625..1250 3p FF UL/CSA (XT2NU3125BBB000XXX) - 3-poles (3P3d) - Rated current 125A - Short circuit rating 18kA (600Vac; UL489) - Thermal-Magnetic (adjustable) (TMA) trip unit - Rated voltage 600Vac - equivalent to XT2N 125TMA 125-625-1250 3pFFUL/CSA / XT2N125TMA12562512503pFFULCSA
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA074746R1
Online Price
$2,765.70
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
1SDA074746R1ABB - Tmax XT UL/CSA
Description
Moulded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax XT (UL/CSA) series) - XT2N 125 TMA 125-625..1250 3p FF UL/CSA (XT2NU3125BBB000XXX) - 3-poles (3P3d) - Rated current 125A - Short circuit rating 18kA (600Vac; UL489) - Thermal-Magnetic (adjustable) (TMA) trip unit - Rated voltage 600Vac - equivalent to XT2N 125TMA 125-625-1250 3pFFUL/CSA / XT2N125TMA12562512503pFFULCSA
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax XT (UL/CSA)
Sub-range name
XT2N
Functions
Moulded Case Circuit Breaker (MCCB)
Poles
3-poles (3P3d)
Rated current
125A
Trip current rating
125 AT
Frame current rating
125 AF
Rated Voltage (DC)
500Vdc
Rated voltage (AC)
600Vac
Rated impulse voltage (Uimp)
8 kV
Connection type
Ring-lug or bar connections
Short circuit breaking rating
65kA (240Vac; UL489)
25kA (480Vac; UL489)
18kA (600Vac; UL489)
25kA (480Vac; UL489)
18kA (600Vac; UL489)
Trip unit type
Thermal-Magnetic (adjustable)
TMA
TMA
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Protection settings
Over-current -- adjustable 0.7...1.0 x In (87.5A...125A)
Short-circuit pickup current -- adjustable 5...10 x In (625A...1250A)
Short-circuit pickup current -- adjustable 5...10 x In (625A...1250A)
Operating mode
Toggle
Electrical durability (with load)
8000 operations
Mechanical durability (at no load)
25 000 operations
Order code / Manufacturer SKU
XT2N 125 TMA 125-625..1250 3p FF UL/CSA
XT2NU3125BBB000XXX
XT2NU3125BBB000XXX
Manufacturer product status
Commercialized
Equivalent to
XT2N 125TMA 125-625-1250 3pFFUL/CSA
XT2N125TMA12562512503pFFULCSA
XT2N125TMA12562512503pFFULCSA
EAN code
8015644787233
UPC code
888614517769
UNSPSC code
39121616
Compliant with standard(s)
UL 489
CSA C22.2
CSA C22.2
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - SACE Tmax XT UL-CSA - Catalogue.pdf | 18 May 2021 | English (US) |
ABB - SACE Tmax XT UL-CSA - Technical characteristics.pdf | 18 May 2021 | English (US) |