ABB
1SDA075364R1XT4N 250 Ekip LS/I In=40A 4p F F UL/CSA (XT4NU4040FFF000XXX)
XT4N 250 Ekip LS/I In=40A 4p F F UL/CSA (XT4NU4040FFF000XXX)
Moulded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax XT (UL/CSA) series) - XT4N 250 Ekip LS/I In=40A 4p F F UL/CSA (XT4NU4040FFF000XXX) - 4-poles (4P4d) - Rated current 40A - Short circuit rating 18kA (600Vac; UL489) - Electronic (Ekip LS/I) trip unit - Rated voltage 600Vac - equivalent to XT4N 250 EKIP LSI IN=40A 4PFFUL/CSA / XT4N250EkipLSIIn40A4pFFULCSA
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
Brand
SKU
1SDA075364R1
Online Price
$4,240.50
Please add this item to cart to request a quote or contact us at [email protected] for product availability.
1SDA075364R1ABB - Tmax XT UL/CSA
Description
Moulded Case Circuit Breaker (MCCB) - ABB / SACE (Tmax XT (UL/CSA) series) - XT4N 250 Ekip LS/I In=40A 4p F F UL/CSA (XT4NU4040FFF000XXX) - 4-poles (4P4d) - Rated current 40A - Short circuit rating 18kA (600Vac; UL489) - Electronic (Ekip LS/I) trip unit - Rated voltage 600Vac - equivalent to XT4N 250 EKIP LSI IN=40A 4PFFUL/CSA / XT4N250EkipLSIIn40A4pFFULCSA
Specifications
Primary brand
ABB
Secondary brand
SACE
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Tmax XT (UL/CSA)
Sub-range name
XT4N
Functions
Moulded Case Circuit Breaker (MCCB)
Poles
4-poles (4P4d)
Rated current
40A
Trip current rating
40 AT
Frame current rating
250 AF
Rated Voltage (DC)
500Vdc
Rated voltage (AC)
600Vac
Rated impulse voltage (Uimp)
8 kV
Connection type
Ring-lug or bar connections
Short circuit breaking rating
65kA (240Vac; UL489)
25kA (480Vac; UL489)
18kA (600Vac; UL489)
25kA (480Vac; UL489)
18kA (600Vac; UL489)
Trip unit type
Electronic
Ekip LS/I
Ekip LS/I
Protection functions
(L) Protection against overload
(S) Protection against short-circuit with time delay OR (I) Instantaneous protection against short-circuit
(S) Protection against short-circuit with time delay OR (I) Instantaneous protection against short-circuit
Protection settings
L - Protection against overload -- adjustable 0.4...1 x In (16A...40A)
S - Protection against short-circuit with time delay -- adjustable 1...10 x In (40A...400A) (with adjustable time trip curve)
I - Instantaneous protection against short-circuit -- adjustable 1...10 x In (40A...400A)
S - Protection against short-circuit with time delay -- adjustable 1...10 x In (40A...400A) (with adjustable time trip curve)
I - Instantaneous protection against short-circuit -- adjustable 1...10 x In (40A...400A)
Operating mode
Toggle
Electrical durability (with load)
8000 operations
Mechanical durability (at no load)
25 000 operations
Order code / Manufacturer SKU
XT4N 250 Ekip LS/I In=40A 4p F F UL/CSA
XT4NU4040FFF000XXX
XT4NU4040FFF000XXX
Manufacturer product status
Commercialized
Equivalent to
XT4N 250 EKIP LSI IN=40A 4PFFUL/CSA
XT4N250EkipLSIIn40A4pFFULCSA
XT4N250EkipLSIIn40A4pFFULCSA
EAN code
8015644793418
UPC code
888614410428
UNSPSC code
39121616
Compliant with standard(s)
UL 489
CSA C22.2
CSA C22.2
Related Documents
Name | Last Update | Language |
---|---|---|
ABB - SACE Tmax XT UL-CSA - Catalogue.pdf | 18 May 2021 | English (US) |
ABB - SACE Tmax XT UL-CSA - Technical characteristics.pdf | 18 May 2021 | English (US) |