Description
Dual-input redundancy module (2 x inputs + 1 x output) with built-in decoupl. MOSFET (for 1+1 or N+1 redundancy) + ATEX approval - PULS (DIMENSION Y-series) - 24-48Vdc (24Vdc / 48Vdc nom.) / 20A output - with screw-clamp connections - DIN rail mounting (32mm width) - equivalent to #YR20246
Specifications
Primary brand
PULS
Main function
Redundancy unit
Product series / family name
DIMENSION series
Sub-range name
Y-series
Functions
Dual-input redundancy module (2 x inputs + 1 x output)
Design
built-in decoupl. MOSFET (for 1+1 or N+1 redundancy)
ATEX approval
ATEX approval
Supply voltage (DC)
18Vdc-35Vdc (24Vdc nom.)
Rated current
20A (at 48Vdc)
Output voltage (DC)
24-48Vdc (24Vdc / 48Vdc nom.)
Connection type
screw-clamp connections
Protection functions
short-circuit protection (26A threshold at 6V)
Series / parallel operation -- 1+1 Redundancy Use of 2 identical power supplies in parallel to provide continued operation following most failures in a single power supply. The 2 power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements.
Series / parallel operation -- 1+1 Redundancy Use of 2 identical power supplies in parallel to provide continued operation following most failures in a single power supply. The 2 power supply outputs should be isolated from each other by utilizing diodes or other switching arrangements.
Net Width (mm)
32 mm
Mounting mode
DIN rail mounting
Dimensions
W32mm x H124mm x D117mm
Ambient air temperature for operation
-40...+70 °C
Power dissipation/losses
(18-35Vdc input; 2x5A input) 2.6 W
(18-35Vdc input; 2x10A input) 5.6 W
(18-35Vdc input; 2x10A input) 5.6 W
Manufacturer product status
Commercialized
Equivalent to
YR20246
Capacitance
(output stage) 320 μF
Compliant with standard(s)
CE marking
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
IECEx
ATEX
Class I Div. 2 HazLoc
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
UL 508
UL 60950-1
IEC 60950-1 CB-Scheme
IECEx
ATEX
Class I Div. 2 HazLoc
EAC Registration
EN 61000-6-1 Immunity for residential environments
EN 61000-6-2 Immunity for industrial environments
EN 61000-6-3 Emission for residential environments
Benefits
For 1+1 Redundancy with automated load sharing
Dual input with single output
Redundancy OK signal included which reports the loss of redundancy
160% (32.5A) peak load capability
Reverse input polarity protection
Full power between -40°C and +70°C
Width only 32mm
Rugged metal housing
Easy wiring;
Distribution terminal for negative pole included
The YR20.246 is a redundancy module for building redundant power supply systems. It is equipped with 2 input channels and 1 output. The 2 inputs are decoupled by MOSFET technology. The device is equipped with an automated load sharing feature which can compensate a small voltage imbalance between the power supplies connected to the inputs in order to achieve an even current share. It also monitors the function of the redundancy circuitry and provides a signal in case of a failure or a high output current which could prevent redundancy if 1 power supply fails. If this feature is not required the YR20.242 is available. The redundancy utilizes MOSFETs instead of diodes for the decoupling of the 2 input channels. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage. Due to the low power losses the unit is very slender and only requires 32mm width on the DIN-rail. Large connection terminals allow for a safe and fast installation. The large international approval package makes this unit suitable for nearly every application
Dual input with single output
Redundancy OK signal included which reports the loss of redundancy
160% (32.5A) peak load capability
Reverse input polarity protection
Full power between -40°C and +70°C
Width only 32mm
Rugged metal housing
Easy wiring;
Distribution terminal for negative pole included
The YR20.246 is a redundancy module for building redundant power supply systems. It is equipped with 2 input channels and 1 output. The 2 inputs are decoupled by MOSFET technology. The device is equipped with an automated load sharing feature which can compensate a small voltage imbalance between the power supplies connected to the inputs in order to achieve an even current share. It also monitors the function of the redundancy circuitry and provides a signal in case of a failure or a high output current which could prevent redundancy if 1 power supply fails. If this feature is not required the YR20.242 is available. The redundancy utilizes MOSFETs instead of diodes for the decoupling of the 2 input channels. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage. Due to the low power losses the unit is very slender and only requires 32mm width on the DIN-rail. Large connection terminals allow for a safe and fast installation. The large international approval package makes this unit suitable for nearly every application
Electrical durability
(at 40°C; 10A output; 2x5A input) 372000 hours
(at 40°C; 20A output; 2x10A input) 182000 hours
(at 25°C; 10A output; 2x5A input) 1053000 hours
(at 25°C; 20A output; 2x10A input) 516000 hours
(at 40°C; 20A output; 2x10A input) 182000 hours
(at 25°C; 10A output; 2x5A input) 1053000 hours
(at 25°C; 20A output; 2x10A input) 516000 hours
Ripple
100-500mVpp (20Hz...20MHz; 50Ω)
MTBF (Mean Time Between Failures)
2306000h (at 40°C; 2x5A input; MTBF SN 29500 IEC 61709)
1954000h (at 40°C; 2x10A input; MTBF SN 29500 IEC 61709)
3913000h (at 25°C; 2x5A input; MTBF SN 29500 IEC 61709)
3359000h (at 25°C; 2x10A input; MTBF SN 29500 IEC 61709)
964000h (at 40°C; 2x5A input; MTBF MIL HDBK 217F GB40)
858000h (at 40°C; 2x10A input; MTBF MIL HDBK 217F GB40)
1379000h (at 25°C; 2x5A input; MTBF MIL HDBK 217F GB25)
1226000h (at 25°C; 2x10A input; MTBF MIL HDBK 217F GB25)
278000h (at 40°C; 2x5A input; MTBF MIL HDBK 217F GF40)
243000h (at 40°C; 2x10A input; MTBF MIL HDBK 217F GF40)
381000h (at 25°C; 2x5A input; MTBF MIL HDBK 217F GF25)
330000h (at 25°C; 2x10A input; MTBF MIL HDBK 217F GF25)
1954000h (at 40°C; 2x10A input; MTBF SN 29500 IEC 61709)
3913000h (at 25°C; 2x5A input; MTBF SN 29500 IEC 61709)
3359000h (at 25°C; 2x10A input; MTBF SN 29500 IEC 61709)
964000h (at 40°C; 2x5A input; MTBF MIL HDBK 217F GB40)
858000h (at 40°C; 2x10A input; MTBF MIL HDBK 217F GB40)
1379000h (at 25°C; 2x5A input; MTBF MIL HDBK 217F GB25)
1226000h (at 25°C; 2x10A input; MTBF MIL HDBK 217F GB25)
278000h (at 40°C; 2x5A input; MTBF MIL HDBK 217F GF40)
243000h (at 40°C; 2x10A input; MTBF MIL HDBK 217F GF40)
381000h (at 25°C; 2x5A input; MTBF MIL HDBK 217F GF25)
330000h (at 25°C; 2x10A input; MTBF MIL HDBK 217F GF25)
Related Documents
Name | Last Update | Language |
---|---|---|
PULS - Power supply units - Catalog.pdf | 01 Oct 2021 | English (US) |
PULS - YR20-246-1 - Datasheet.pdf | 01 Oct 2021 | English (US) |